Electronis TSP’s | Unit is overflowing out of DU. Runs for about half an hour once a week. | The unit should only run for about a second several times a day. Running for half an hour is to much water. The timer can adjust run time. |
MI-100 | Are these trap seal primers CSA aproved? | The MI-100 is UPC and ASSE aproved, but not CSA at this time. |
MR-500 | How can you tell which cartridge you have in the MR-500? | The cartridges are color coated. The MR-500 cartridge is red, the M1-500 is red, and the M2-500 is black. |